Full width drawer operation method

2024-10-29

● Open the unit door, push the drawer along the guide rail and close the unit door;

● Press the position to operate the unlocking button (hereinafter referred to as the unlocking button), swing the rocker clockwise to the test position, and the unlocking button will pop out and reset;

● Press the unlock button again, swing the rocker clockwise to the connected position, and the unlock button will pop out and reset;

● Take out the rocker and move the unlocking button to the left (hereinafter referred to as the moving button) to close the rocker hole and lock the unlocking button at the same time. At this time, the main switch can be closed;

● After the main switch is switched off, push the moving button to the right, press the unlocking button, insert the rocker, shake counterclockwise from the connection to the test position, and the unlocking button will be reset and pop out;

● Press the unlock button again and shake the rocker counterclockwise. When it reaches the isolation position, the unlock button will pop out and reset;

● Take out the rocker, open the unit door, and lift up the drawer to lock the handle to remove the drawer.

 

Full width drawer

This series of drawers is available in four heights of 1U/1.5U/2U/3U (U = 200mm). This series of drawers consists of fixed parts and moving parts (connectors). After the drawer fixing part is pushed into the switch cabinet unit compartment, insert the rocker to insert the drawer
The movable part shall be switched between isolation, test and connection positions in sequence. And the position status of the connector is displayed by the indication window with LED.

No matter manual or electric, the drawer door panel and switch have mechanical interlocking mechanism, that is, no matter manual or electric scheme, as long as the switch is in the closing position, the drawer assembly door cannot be opened.