Method of operation of drawers with electrically operated circuit breakers:
2024-10-29
● Open the unit door, push the drawer along the guide rail and close the unit door;
● Press the unlocking button, swing the rocker clockwise to the test position, and the unlocking button will pop out and reset;
● Press the unlock button again, swing the rocker clockwise to the connected position, and the unlock button will pop out and reset;
● Take out the rocker and move the moving button to the left to close the rocker hole and lock the unlocking button at the same time;
At this time, press the closing button of the electric operating mechanism to close the main switch;
● After opening the main switch through the electric operating mechanism, push the moving button to the right, and then the rocker hole will be opened to release the unlocking button;
● Press the unlock button, insert the rocker, shake counterclockwise from the connection back to the test position, and the unlock button will be reset and pop out;
● Press the unlocking button again, shake the rocker counterclockwise to the isolation position, and the unlocking button will also pop out and reset;
● Take out the rocker, open the unit door, and lift the drawer up to lock the handle to move out of the drawer;
● If the main switch is not disconnected or the rocker hole is not closed due to misoperation. To move out of the connection position, the position-operated unlock button must be pressed, which will trigger the opening of the main switch, thus ensuring that the drawer can only be moved when the main switch is in the open state.